FluesAn Oil-fired AGA requires some form of flue or chimney, so as to safely remove the natural products of combustion, at the same time taking cooking smells and steam from the ovens. For the AGA to work properly, the chimney must be constructed of the the appropriate materials and rise to a satisfactory height, whilst complying with current legislation, such as the Building Regulations. The need for access to a chimney will probably dictate the position chosen for the AGA, and we would strongly advise that your local AGA Distributor be asked to carry out a survey of the proposed site.
Two main chimney arrangements are available (see illustration below):
|
|||
VentilationLike all oil fired appliances, the AGA requires a permanent air supply into the kitchen to provide both air for combustion and also to enable the chimney to operate. A permanent opening of 29 sq.cm ( 4.5 sq.inch) free area is required and normally a 6" x 9" brick will provide this amount. Extractor fans and stove hoods do not give a supply of air into the room, as they are busy sucking it out, as do other appliances such as a tumble dryer. If other combustion appliances are fitted in the same room as the AGA, then additional ventilation will be required. |
|||
PlumbingWith most models of AGA, you have the option of obtaining domestic hot water. This provides an economic way of producing either 410 litres (90 gallons) of hot water, spread out over a 24 hour period, regardless of how much cooking is carried out. With the 2 oven oil fired AGA only, there is an optional larger boiler available, which will increase the domestic hot water output to 614 litres (135 gallons) over the same 24 hour period. Hot water is generated within the AGA and circulates through a conventional, open vented, gravity system into a 190 litre storage cylinder, located within 5 metres of the AGA. With the larger 135 boiler, a correspondingly increased, 280 litre, storage cylinder is required.
Does the AGA produce domestic hot water for free? Will the hot water demands affect
the AGA’s
cooking performance? What happens if we do not use all the hot water produced by the AGA? What if we need more hot water than the AGA will produce? Can we fit a thermostat to the AGA to control the hot water temperature? Can the AGA be used to supply a radiator? What about a towel rail? What happens in a hard water area? Can the AGA be connected to a ‘sealed’ hot
water system? Can a boiler be fitted to an existing ‘dry’ AGA? We no longer want hot water from our AGA. Can we just disconnect the boiler? The water supply to the house is to be off for a short while. What should we do? |
|||
Flue/ChimneyMay require the AGA to be close to an existing chimney or against an outside wall. See separate sheets on flues/chimney/ventilation. |
|||
Floor/Hearth/PlinthThe floor must be strong enough to carry the weight of the AGA, typically: 2 Oven 406kg (8cwt) Where an AGA Electric or Gas Module is attached add 129kg (2.5cwt) The hearth must be non combustible for a thickness of at least 12mm A raised plinth is not essential, and there is no reason why an AGA shouldn’t sit on the normal floor ( providing it meets the above criteria). If a higher working position is preferred, or the finished height needs to match adjacent work surfaces, then a cast concrete slab, usually 50mm thick, is the answer. The slab dimensions should be the same as the base of the AGA: 2 oven 987 x 679mm The 679 dimension can be reduced slightly if the front of the plinth is to be tiled. Alternatively, there are also three purpose made plinths available to suit either a 2 oven gas or oil fired AGA, the hot cupboard (for the 4 oven AGA) and another for the gas and electric Modules. Whatever type of hearth is chosen, it must be absolutely level in all directions.
|
|||
ClearancesAn oil-fired AGA requires an oil control valve to be fitted on its left or right hand side. (Note. If an AGA module is also installed then the valve must be fitted to the R.H side) This valve requires easy access for adjustment and servicing, therefore if the AGA is to be installed in a recess, increased width clearances are needed, significantly larger than the actual AGA dimensions. In this view the oil control valve is shown on the left hand side of a 2 oven stove. Total Clearance required = 1303mm. (i.e.AGA width 987 mm + oil valve access 200 mm + door opening clearance 116 mm). If the right hand wall does not protrude forward beyond the front of the AGA, then there is no need for a clearance here. In this case the Total clearance required would be 1187mm. (i.e. AGA width 987mm + valve clearance 200mm). Had the valve been installed on the right hand side, there would be no need for a gap on the left, therefore the Total Clearance required = 1187mm, whether or not the right hand wall extends forward. For a 4 oven AGA, add 500mm to stove width in the above calculations. If the AGA is to be installed in a tight brick recess, then the minimum clearances should be increased by at least 10mm on either side, to allow for the walls being out of square and also for the natural dimensional variations found in castings. If the AGA is not going into a tight recess, but merely between kitchen work units, then there is no reason why the units cannot be brought up to the side of the AGA, with the Oil control valve being actually located in the cupboard, the latter having a false wall. Zero clearances are then required. Under some special circumstances, it may be possible to site the oil control valve remotely from the AGA, but the distance from the burner must not exceed 3 metres. Work tops should however stop short of the AGA top plate and not actually touch it. Any slight gap can be filled with a silicone sealant. If the surrounding walls are to be tiled, then this must be done before the AGA is installed, as the tiles must be taken down below the AGA top plate level, not finish above it. The rear wall must be non combustible for at least 25mm thickness. At least 60mm clearance should be allowed above the insulating covers in their vertical, open position. |
|||
Electricity SupplyA 240 volt 3 amp supply is required to operate the thermostatic control. This is best provided by a 13 amp socket, located at low level, adjacent to the Oil control Valve. If a 4 oven AGA is fitted with the gas or electric hob option in its hot cupboard, then an additional 13 amp electrical supply will be required at high level. |
|||
AGA DimensionsMaximum depth over handrail etc 756mm |
|||
Heat to RoomThe AGA releases a gentle warmth into the kitchen, which is not likely to give rise to any problems, unless the room is exceptionally small or poorly ventilated. The actual output varies slightly from model to model and in accordance with the type of flue system chosen. An average contribution to the room of 1 kW/hr should be allowed. |
|||
Fuel SupplyOil storage and supply line Storage
tank
The fuel must flow by gravity to the AGA, therefore the tank must be sited at a higher level than the stove, with the base of the oil tank not less than 450mm above the base of the AGA, but the top of the oil tank not higher than 3.2m above the base of the AGA. Only a bottom outlet tank must be used. If the tank cannot be sited higher than the AGA, then as a last resort, a proprietary ‘Oil lifting’ device can be used, but this introduces essential dependence on electricity for the AGA operation. De-aeration devices, ‘Tiger Loops’ or 2 pipe systems cannot be used with an AGA. Fuel
Pipe Filter
|
|||
Fuel
|









